United Faith Sdn Bhd (HQ)
6 (Ground Floor), Jalan BPU 6, Bandar Puchong Utama, 47100 Puchong, Selangor, Malaysia.
+6012-2631315
+6012-5992610

SG Branch :
United Faith Pte Ltd

7030, Ang Mo Kio Ave 5, #01-23, Northstar@AMK, Singapore 569880.
+65-9106 6813

KL Branch :
8G, Jalan Pandan 2/3, Pandan Jaya, 55100 Kuala Lumpur, Malaysia.
+6012-491 2610

PJ Branch :
13, Jalan 21/37, SS 2, 47300 Petaling Jaya, Selangor, Malaysia.
+6012-599 2610

i-Vu® VVT Zone II Controller OPN-VVTZC-02

Previous 7 / 29 Next

i-Vu® VVT Zone II Controller OPN-VVTZC-02 Carrier BACNet HVAC Controllers Air Conditioning Control System


Product Integrated Controller

The VVT Zone II controller provides zone level temperature and air quality control for a variety of pressure-dependent VVT applications. This advanced controller features a separable actuator for easy installation onto single duct and parallel fan-powered air terminals. It also features native BACnet communications and plug-and-play connectivity to the Carrier i-Vu Building Automation System.


carrier-bacnet-international-member
carrier-bacnet-testing-laboratories

Application Features

  • Sophisticated factory-engineered and tested algorithms provide reliability and energy efficiency
  • Pressure dependent space temperature control
  • Supports modulating hot water, 2-position hot water, single, 2, or 3 stage electric heat, or zone perimeter heat
  • Built-in advanced control routines for zone level humidity control or zone level demand control ventilation (ASHRAE® 62)
  • Adaptive optimal start and PID control for maximum occupant comfort
  • Supports Carrier communicating room sensors, which allow for local setpoint adjustment and local overrides

System Benefits

  • Integrated Carrier airside linkage algorithm for plug-and-play integration with Carrier air sources
  • Fully plug-and-play with the Carrier i-Vu Building Automation System
  • Supports demand limiting for maximum energy savings
  • Compatible with i-Vu Tenant Billing for tracking tenants’ after-hours energy usage

Hardware Features

  • Separable brushless actuator for reliability and longevity
  • Capable of system or stand-alone operation
  • Native BACnet MS/TP or ARCnet communications
BACnet Support Conforms to the Advanced Application Controller (B-AAC) Standard Device Profile as defined in BACnet 135-2012 Annex L Protocol rev. 9
Communication Ports BACnet Port: EIA-485 port for BACnet MS/TP communications (9600 bps, 19.2 kbps, 38.4 kbps, & 76.8) or ARCnet 156 kbps
Local Access Port: For system start-up and troubleshooting (115.2 kbps)
Rnet Port: For connecting Carrier communicating room sensors and Carrier's touchscreen user interface
ARCnet Port: For connecting the actuator cable
Separable Actuator Brushless DC motor, torque 35 inch-pounds (4Nm), runtime 205 seconds for 90 degree travel during control.
Integral Pressure Sensor Precision low flow AWM series O-2 in H2O, sensitive down to +/-0.001 in. H2O. Barbed tapered airflow connections accept 3/16 in. (4.75 mm) ID tubing. Allows for readings across the 0-2 in H2O range, accurate to +/-5% of full flow at 2 in. H2O.
Inputs 3 analog inputs: RH/CO2 (0-5V), T55 (10k thermistor), SAT (10k thermistor). AIs have 10 bit A/D resolution.
1 binary input: Remote Occupancy (dry contact).
Outputs 1 analog input:Hot Water Valve (HWV). AO is 0 to 10VDC (5mA maximum) with 8 bit D/A resolution using filtered PWM.
3 binary outputs: HEAT1, HEAT2, and FAN. Relay contact rated at 1A max @ 24VAC/VDC, configured normally open.
Protection Incoming power and network connections are protected by non-replaceable internal solid state polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input and output connections are also protected against voltage transient and surge events.
Battery 10-year lithium CR2032 battery provides a minimum of 10,000 hours of trend data retention during power outages.
Status Indicators LED status indicators for BACnet MS/TP communication, run status, error, power and all digital outputs
Controller Addressing Rotary DIP switches set BACnet MS/TP address of controller.
Listed by UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE EN50082-1997, UL94-5VA plenum rated enclosure
Environmental Operating Range Operating: 32° to 130°F (0° to 54°C) 10 to 90% RH, non-condensing
Storage: -24° to 140°F (-30° to 60°C) 10 to 90% RH, non-condensing
Power Requirements 24VAC +/- 10%, 50-60Hz, 14 VA power consumption, 26VDC (25V min, 30V max), single class 2 source only, 100 VA or less

Please leave your enquiry here, we will reply as soon as possible.
Name*  
Company Name  
Product Interested  
Quantity  
Email*  
Contact No.*  
Attachment  
*only support gif, jpeg, jpg, png, pdf
Messages*  

Switch to Mobile Version
Subscribe Newsletter